V8/TS2060 series Error HKFAQ000108

date: 2021/7/27

Communication error "Timeout"

This error is displayed when the V/TS series does not receive an answer from a connected device (PLC, temperature controller, etc.) within the predetermined time after issuing a request to send.

 

[In cases where the error occurs before communication]

<Causes>

  1. The communication cable is not connected correctly or is disconnected.
  2. Communication settings on the V/TS series do not match those of the connected device.

 

<Solutions>

  1. Check the cable connection.
  2. Check that the selection of [Maker] and [Series] on the V/TS series is correct and that the communication settings including baud rate, data length, stop bit, and parity are the same between the connected device and the V/TS series.

     

V8/TS series

Setting location: V-SFT-6 editor [System Setting] → [Hardware Setting] → [PLCx Properties]



V7/V6 series

Setting location: V-SFT-5 editor [System Setting] → [PLC Communication] → [PLC Model], [Communication Parameter]
V8series|Communication error Timeout

V8series|Communication error Timeout

V8series|Communication error Timeout

 

[In cases where the error occurs during normal communication]

<Cause>

Data may be disrupted because of noise.

 

<Solution>

Provide protection against noise.

Was this page helpful?

Please cooperate with the questionnaire to make it better.

  • Back to FAQ top

FAQ by product

  • V10/V9 series

  • V8/TS2060 series

  • TELLUS and V-Server

Most searched FAQs

  • Communication error "Error code received"
  • I want to search where these buttons are used:
    - Screen Change-over buttons
    - Overlap Control buttons
  • Communication Error "Timeout"
  • "The port cannot be opened."
  • What PLC models can be connected?
To page top
  • » Inquiries about products
  • » Inquiries about sales
  • » Request for catalogs
  • » Compliance with the RoHS

MONITOUCH

LINE UP
  • X1 SERIES
  • V10 SERIES
  • V9 SERIES
  • TECHNOSHOT
  • Web Machine Interface
  • Smart Editor
  • V-SFT
  • TELLUS and V-Server
Support »
  • Download
  • Inquiries
  • Recommended peripheral equipment
FAQ »
  • FAQ concerning MONITOUCH
Distributors »
  • Overseas distributors
  • » Privacy Policy
Copyright©2013 Hakko Electronics Co., Ltd. All Right Reserved