V10/V9 series Error HKFAQ000314

date: 2024/8/27

The error "It is beyond the limits of the data." occurs in the V-SFT error check during editing of a screen that connects to MICREX-SX.

An invalid device memory is set in the screen program.

Cause 1:

X/Y device memory, P/PE link, or FL-Net device memory is specified but the SX device memory information file (.ini file) has not been imported into V-SFT (when the loader software is SX Programmer Standard).

 

Cause 2:

Linking with the SX project was unsuccessful (when the loader software is SX Programmer Expert).

 

Cause 3:

The CPU number and the SX station number in the device memory specified in V-SFT do not match the settings on the SX side.

 

 

For cause 1:

Import the SX device information file (.ini) according to the following procedure.
If the file has already been imported, check that the selected file is correct.

  1. Export the device information file (.ini) from SX Programmer Standard.

    [Project] → [Export] → [Device Information]


    * An .ini file and a folder with the same name as the .ini file are created in the same folder. If the .ini file needs to be moved, move the file together with the folder of the same name.


  2. Import the device information file (.ini) into V-SFT.

    [MICREX] → [Import]


    * Selecting the [Store the Project information in the screen data] checkbox allows device memory to be deployed normally even without the .ini file when the screen program is read from the MONITOUCH. If this checkbox is not selected, the .ini file must always be stored at the specified path.


  3. Click [Tool] → [Error Check] to check for device memory errors.

 

  • For cause 2:

    Check the following points.

    • Is the linked project file correct?
    • Are the resource name and worksheet name/group name correct?

If the linked project or reference target is incorrect, select the correct files.

 

For cause 3:

Check that the device memory settings in V-SFT match the settings on the SX side.

When the loader software is SX Programmer Standard

M, L, SM: Check that the CPU number is correct.

  • Word designation: CPU No. 0, WM100 (M1000 to 100F)

          CPU No.
     
  • Bit designation: CPU No. 0, M1000

          CPU No.

 

X, Y: Check that the SX station number is correct.

  • Word designation: SX station number 0, WX100 (X1000 to 100F)

        SX station number

  • Bit designation: SX station number 0, X1000

        SX station number

 

When the loader software is SX Programmer Expert and AT designation is used

%M1, %M3, %M10: Check that the CPU number is correct.

  • Word designation: %MW1, CPU No. 1, word address 100

          CPU No.
     
  • Bit designation: %MX1, CPU No. 1, word address 100, bit address 0

          CPU No.

 

%I, %Q: Check that the SX station number is correct.

  • Word designation: %IW, SX station number 1, word address 100

        SX station number

  • Bit designation: %IX, SX station number 1, word address 100, bit address 0

        SX station number

 

 

Was this page helpful?

Please cooperate with the questionnaire to make it better.

Related questions(FAQ)

  • I want to connect to MICREX-SX but "Communication Error: Error Code received " occurs.
  • Back to FAQ top

FAQ by product

  • V10/V9 series

  • V8/TS2060 series

  • TELLUS and V-Server

Most searched FAQs

  • Communication error "Error code received"
  • I want to search where these buttons are used:
    - Screen Change-over buttons
    - Overlap Control buttons
  • Communication Error "Timeout"
  • "The port cannot be opened."
  • What PLC models can be connected?
To page top
  • » Inquiries about products
  • » Inquiries about sales
  • » Request for catalogs
  • » Compliance with the RoHS

MONITOUCH

LINE UP
  • X1 SERIES
  • V10 SERIES
  • V9 SERIES
  • TECHNOSHOT
  • Web Machine Interface
  • Smart Editor
  • V-SFT
  • TELLUS and V-Server
Support »
  • Download
  • Inquiries
  • Recommended peripheral equipment
FAQ »
  • FAQ concerning MONITOUCH
Distributors »
  • Overseas distributors
  • » Privacy Policy
Copyright©2013 Hakko Electronics Co., Ltd. All Right Reserved