date: 2021/8/3
How to replace a Fuji Electric UD series unit with a MONITOUCH
Screen programs and the panel cut-out are not compatible between the UD series and MONITOUCH.
Screen programs must be recreated.
For the detailed specifications and handling procedure of the UD series, consult with the Fuji Electric PLC Department.
UD10/UD15 → TS2060i/TS2060
The panel cut-out dimensions must be made larger.
Model |
UD10 |
UD15 |
TS2060(i) |
External dimensions |
144 x 72 x 56.5 |
144 x 75 x 92 |
182.5 x 138.8 x 45.8 |
Panel cut-out |
138 x 68 |
174 x 131 |
|
Resolution (dots) | 100 x 32 | 160 x 80 | 320 x 240 |
UD20/UD21 → TS2060i/TS2060
The panel cut-out dimensions are smaller.
Model |
UD20 |
UD21 |
TS2060(i) |
External dimensions |
266 x 150 x 83 |
182.5 x 138.8 x 45.8 |
|
Panel cut-out |
255.5 x 139.5 |
174 x 131 |
|
Resolution (dots) | 256 x 128 | 320 x 240 |
UD25 → TS2060i/TS2060
The panel cut-out dimensions are smaller.
Model |
UD25 |
TS2060(i) |
External dimensions |
200 x 150 x 62 |
182.5 x 138.8 x 45.8 |
Panel cut-out |
192.5 x 142.5 |
174 x 131 |
Resolution (dots) | 320 x 240 |
UD30 → TS2060i/TS2060
The panel cut-out dimensions are smaller.
Model |
UD30 |
TS2060(i) |
External dimensions |
266 x 150 x 83 |
182.5 x 138.8 x 45.8 |
Panel cut-out |
255.5 x 139.5 |
174 x 131 |
Resolution (dots) | 256 x 128 | 320 x 240 |
UD40/UD45 → V9080iCD/V9100iC
When replacing with a V9080, the panel cut-out dimensions are smaller.
When replacing with a V9100, the vertical dimension of the panel cut-out is larger and the horizontal dimension is smaller.
Model |
UD40 |
UD45 |
V9080iCD |
V9100iC |
External dimensions |
330 x 220 x 94 |
330 x 220 x 111 |
235 x 180 x 48.9 |
303.8 x 231 x 54 |
Panel cut-out |
316 x 206 |
220.5 x 165.5 |
289 x 216.2 |
|
Resolution (dots) | 640 x 400 | 640 x 480 |
UD41/UD46 → V9080iCD/V9100iC
When replacing with a V9080, the panel cut-out dimensions are smaller.
When replacing with a V9100, the vertical dimension of the panel cut-out is larger and the horizontal dimension is smaller.
Model |
UD41 |
UD46 |
V9080iCD |
V9100iC |
External |
315 x 215 x 85 |
235 x 180 x 48.9 |
303.8 x 231 x 54 |
|
Panel cut-out |
300 x 200 |
220.5 x 165.5 |
289 x 216.2 |
|
Resolution (dots) | 640 x 400 | 640x 480 | 640 x 480 |
<Notes>
-
The "CUR-01" communication unit* is required to establish T-link connection with a PLC.
-
The "CUR-00" communication unit* is required to establish OPCN-1 connection with a PLC.
* Note that the TS2060 (non-i type) is not supported.
Was this page helpful?
Please cooperate with the questionnaire to make it better.