V8/TS2060 series Error HKFAQ000336

date: 2021/11/17

"Error:161 (24:x)"

This error is displayed when the SRAM area is not formatted on the V8/TS series unit.

 

<Causes>

The following conditions cause this error.

 

A.     When a screen program that uses SRAM is transferred for the first time after
        purchase

B.      When the battery voltage drops and the SRAM area is erased on MONITOUCH
         to which a screen program that uses SRAM has been transferred

 

<Solutions>

Case A

Format the SRAM area.

Perform formatting on the [Main Menu] → [SRAM/Clock] Adjustment screen in Main Menu screen on the V8/TS series unit.
For information on the format procedure, click here.

 * For V8 series,  be sure to set the battery.
    For information on the battery mounting procedure, click here.

 

Case B

The message "Battery not set" or "Brownout of Battery"  is displayed at the lower in the Main Menu screen on the V8/TS series unit.

 

Purchase a battery and perform battery replacement.

  • V8 series
       Battery type: V7-BT
  • TS2060 series
       Battery type: TS-BT(CR2032W/CR2032X)
  • TS1000S series
       Battery type: CR2032

 For information on the battery replacement procedure:

  • For V8 series, click here.
  • For TS2060 series, click here.
  • For TS1000S series, click here.

 

The error does not disappear just by replacing the battery. Always format the SRAM area.
For information on the format procedure, click here.

 

* If Error: 161 (24: x) appears due to a battery voltage drop, all data stored in
   SRAM is erased. The data cannot be restored.
   The service life of the battery is about 5 years. Replace the battery before the end
   of its service life.

Was this page helpful?

Please cooperate with the questionnaire to make it better.

Related questions(FAQ)

  • "Battery voltage drop", "Brownout of Battery", "Battery changeover required", "Battery not set"
  • Back to FAQ top

FAQ by product

  • V10/V9 series

  • V8/TS2060 series

  • TELLUS and V-Server

Most searched FAQs

  • Communication error "Error code received"
  • I want to search where these buttons are used:
    - Screen Change-over buttons
    - Overlap Control buttons
  • Communication Error "Timeout"
  • "The port cannot be opened."
  • What PLC models can be connected?
To page top
  • » Inquiries about products
  • » Inquiries about sales
  • » Request for catalogs
  • » Compliance with the RoHS

MONITOUCH

LINE UP
  • X1 SERIES
  • V10 SERIES
  • V9 SERIES
  • TECHNOSHOT
  • Web Machine Interface
  • Smart Editor
  • V-SFT
  • TELLUS and V-Server
Support »
  • Download
  • Inquiries
  • Recommended peripheral equipment
FAQ »
  • FAQ concerning MONITOUCH
Distributors »
  • Overseas distributors
  • » Privacy Policy
Copyright©2013 Hakko Electronics Co., Ltd. All Right Reserved