V10/V9 series Questions about HKFAQ000037

date: 2021/8/31

How to change-over the screen according to a PLC (external) command

Use [Displaying Screen Device].

* For V8-compatible screen programs, use [Read Area].

 

  1. Check the [Displaying Screen Device] setting located at [System Setting] → [Hardware Setting] → [Control Area] in the screen program.




  2. Set the screen number to [Displaying Screen Device].

    [Displaying Screen Device]

    V9series|How to change-over the screen according to a PLC (external) command

    This will change the screen to the set screen number.

 

If the [Control Area] menu is absent from the hardware settings

[Control Area] is not used for screen programs converted from V8 series and earlier models. In this case, change screens using [Read Area].

[Read Area] setting location

[System Setting] → [Hardware Setting] → [Read/Write Area] → [Read Area]


 

Command method for changing screens

Set the screen number of the target screen to "n+2" in [Read Area] and then turn ON the "n+1-14" bit in [Read Area].


For the example in the above figure

D00002 = 10             Set the target screen number to 10.
D00001-14 bit ON      Turn on the change trigger.

 

Was this page helpful?

Please cooperate with the questionnaire to make it better.

Related questions(FAQ)

  • How to check the number of the screen currently displayed
  • The screen is not switched according to the command from the PLC (external).
  • Back to FAQ top

FAQ by product

  • V10/V9 series

  • V8/TS2060 series

  • TELLUS and V-Server

Most searched FAQs

  • Communication error "Error code received"
  • I want to search where these buttons are used:
    - Screen Change-over buttons
    - Overlap Control buttons
  • Communication Error "Timeout"
  • "The port cannot be opened."
  • What PLC models can be connected?
To page top
  • » Inquiries about products
  • » Inquiries about sales
  • » Request for catalogs
  • » Compliance with the RoHS

MONITOUCH

LINE UP
  • X1 SERIES
  • V10 SERIES
  • V9 SERIES
  • TECHNOSHOT
  • Web Machine Interface
  • Smart Editor
  • V-SFT
  • TELLUS and V-Server
Support »
  • Download
  • Inquiries
  • Recommended peripheral equipment
FAQ »
  • FAQ concerning MONITOUCH
Distributors »
  • Overseas distributors
  • » Privacy Policy
Copyright©2013 Hakko Electronics Co., Ltd. All Right Reserved