V8/TS2060 series Error HKFAQ000119

date: 2022/4/22

"Receive timeout"

This error may be displayed on the configuration software V-SFT when data is transferred.
Possible causes and solutions are given below.

 

[When the transfer cable "USB" is used]

<Causes>

The USB ladder transfer function is being used but the following action is not taken (TS/V8 series only).

  1. The Main Menu screen is not displayed.

  2. "Ladder Transfer Setting" is not offline.

<Solutions>

  1. Display the Main Menu screen.
    (Ladder communication is enabled on the RUN screen only.)

  2. Open "Ladder Transfer Setting" and press [OFFLINE].
    The screen changes as follows when [OFFLINE] is pressed.

 

[When the transfer cable "Ethernet" is used]

<Causes>

  1. The LAN cable is not connected.

  2. "Disconnect" is displayed at the bottom left of the Main Menu → Ethernet screen.

    V8series|Receive timeout
  3. The IP address set on the [Transfer]→[Communication Setting] dialog is not consistent with the IP address of the TSi/V series.

  4. The PC and the TSi/V series are not on the same network.

<Solutions>

  1. Check if the LAN cable is connected to the LAN connector correctly.

  2. "Disconnect" displayed at the bottom left of the Main Menu → Ethernet screen must be changed to "Connect".
    V8series|Receive timeout
    • Depending on whether the hub is used or not, the cable type to use varies.
      Check the cable in use.
      - With hub: Straight cable
      - Without hub: Cross cable

    • When a hub is used, check the LED that indicates the hub link condition.
      If not lit, check the cable, and insert it into another empty port on the hub.

    • Turn on the hub again.

    • Check for errors in setting, such as exchanged data between the subnet mask and default gateway of the TSi/V series.

       

  3. Check the IP address of the TSi/V series on the Main Menu → Ethernet screen, and set it on the [Transfer]→[Communication Setting] dialog.



  4. Check a ping from the PC to the TSi/V series.
    If not pinged, check the IP addresses of the PC and the TSi/V series.

    Example: When checking or changing the IP address of the PC

 

[When the transfer cable "V-CP" is used]

<Causes>

  1. The transfer cable "V-CP" is not connected correctly.
  2. The COM port number set on the [Transfer]→[Communication Setting] dialog is not consistent with the COM port number of the PC.
  3. MJ1 is being used for another function; however, the Main Menu screen is not displayed.
  4. "Editor : MJ1" is not displayed at the bottom left of the Main Menu screen.
  5. "Modem Connect Mode" is displayed at the bottom left of the Main Menu screen.

 

<Solutions>

  1. Check if the transfer cable "V-CP" is connected correctly to the MJ1 port of the TS2060/V series.
     * MJ2 port cannot be used for transfer.

  2. Check the COM port number using the Device Manager of the PC, and set this port number for [Communication Port] on the [Transfer] →[Communication Setting] dialog.

    [COM port on the PC]
    Example: When USB-serial converter is used:

 


  1. [Communication Setting] dialog


  2. When MJ1 is being used for another function as well, be sure to display the Main Menu screen before data transfer.

  3. When the serial ladder transfer function is being used, the indication at the bottom left of the Main Menu screen changes to "Editor : ---".
    Hold down the function switch [F2] until "Editor : MJ1" is displayed, then transfer data again.


    Example: V8 series

    Screen transfer not possible (ladder transfer possible)
    V8series|Receive timeout

    Screen transfer possible
    V8series|Receive timeout

     

    V8series|Receive timeout To keep "Editor : MJ1" at the bottom left of the Main Menu screen at all times, set the screen data as shown below.

     

    TS/V8 series
    Click  [System Setting] → [Hardware Setting] → [Ladder Transfer] .

    Check [Detail Setting] →  [Ladder Communication is not Used in Local Mode] on the [Ladder Transfer Setting] dialog.

    V7 series
    Select [System Setting] → [Extended Communication] → [Ladder Tool] and check [Ladder Communication is not Used in Local Mode].

    V8series|Receive timeout

     

  4. When "Modem Connect Mode" is displayed, press the function switch [F5] and "Editor : MJ1" at the same time to switch to the Extended Function Setting screen.
    Select "Not used" for [Modem Comm. Baud Rate] and press [Setting Finished] to move back to the Main Menu screen.
    When "Modem Connect Mode" is not displayed, transfer data again.
    For more information on the procedure, click here.

 

Was this page helpful?

Please cooperate with the questionnaire to make it better.

  • Back to FAQ top

FAQ by product

  • V10/V9 series

  • V8/TS2060 series

  • TELLUS and V-Server

Most searched FAQs

  • Communication error "Error code received"
  • I want to search where these buttons are used:
    - Screen Change-over buttons
    - Overlap Control buttons
  • Communication Error "Timeout"
  • "The port cannot be opened."
  • What PLC models can be connected?
To page top
  • ≫ 產品諮詢
  • ≫ 營業銷售諮詢
  • ≫ 索取産品目錄
  • ≫ 支援RoHS指令

MONITOUCH

LINE UP
  • X1 SERIES
  • V10 SERIES
  • V9 SERIES
  • TECHNOSHOT
  • Web Machine Interface
  • Smart Editor
  • V-SFT
  • TELLUS and V-Server
服務中心 ≫
  • 下載
  • 諮詢
  • 推薦外圍設備
FAQ(常見問題) ≫
  • FAQ concerning MONITOUCH
代理商 ≫
  • Overseas distributors
  • ≫ Privacy Policy
Copyright©2013 Hakko Electronics Co., Ltd. All Right Reserved