V10/V9 series Operation Troubles HKFAQ000020

date: 2025/1/15

The lamp lights up even though the bit in the lamp device memory is not ON (OFF).

 

<Cause>

The lamp device memory is used redundantly.

<Solution>

Check if the same address as the lamp device memory is used in the screen data or in the PLC program.
Depending on the value set for [No. of Patterns], the number of device memory addresses used will vary.Check the availability of these memory addresses.

 

Example: When five lamps (No. of Patterns: 3) are configured
consecutively from lamp device memory M0000 (bit):

V9series|The_lamp_lights_up_even_though_the_bit_in_the_lamp_device_memory_is_not_ON.

 

  OFF             ON            P3

V9series|The_lamp_lights_up_even_though_the_bit_in_the_lamp_device_memory_is_not_ON.

 

    Wrong                         Correct

V9series|The_lamp_lights_up_even_though_the_bit_in_the_lamp_device_memory_is_not_ON.

When "3" is set for [No. of Patterns], 2 bits are used.

  • L1 (M0000/M0001)
  • L2 (M0002/M0003)
  • L3 (M0004/M0005)
  • L4 (M0006/M0007)
  • L5 (M0008/M0009)

As the number of patterns is increased, the number of bits used is also increased.

 

L1 lamp example:

  • OFF display M0000 : OFF, M0001 : OFF
  • ON display M0000 : ON, M0001 : OFF *
  • P3 display M0000 : OFF, M0001 : ON

* Since the higher bits have priority, P3 display is shown when M0001 is ON.

Was this page helpful?

Please cooperate with the questionnaire to make it better.

Related questions(FAQ)

  • How to search for device memory addresses specified for items used on the screen
  • Back to FAQ top

FAQ by product

  • V10/V9 series

  • V8/TS2060 series

  • TELLUS and V-Server

Most searched FAQs

  • Communication error "Error code received"
  • I want to search where these buttons are used:
    - Screen Change-over buttons
    - Overlap Control buttons
  • Communication Error "Timeout"
  • "The port cannot be opened."
  • What PLC models can be connected?
To page top
  • ≫ 產品諮詢
  • ≫ 營業銷售諮詢
  • ≫ 索取産品目錄
  • ≫ 支援RoHS指令

MONITOUCH

LINE UP
  • X1 SERIES
  • V10 SERIES
  • V9 SERIES
  • TECHNOSHOT
  • Web Machine Interface
  • Smart Editor
  • V-SFT
  • TELLUS and V-Server
服務中心 ≫
  • 下載
  • 諮詢
  • 推薦外圍設備
FAQ(常見問題) ≫
  • FAQ concerning MONITOUCH
代理商 ≫
  • Overseas distributors
  • ≫ Privacy Policy
Copyright©2013 Hakko Electronics Co., Ltd. All Right Reserved