Fuji Electric Co.,LTD
Global
Hakko Electronics (Taiwan)
Select Region
  • Global
  • Europe
  • Japan
  • China
  • Asia
    • Taiwan
    • Korea
Print
Font Size
  • Small
  • Medium
  • Large
  • 首頁
  • HMI
  • 公司簡介
  • ≫ 產品情報
  • ≫ 服務中心
  • ≫ FAQ(常見問題)
  • ≫ 代理商
  1. 首頁 >
  2. 產品情報
V10/V9 series Operation Troubles HKFAQ000028

date: 2017/9/13

Pressing the reset switch does not clear history data.

 

<Causes>

  1. The switch is not pressed twice.
  2. The switch is disabled according to the interlock setting.

 

<Solutions>

  1. Press the "Reset" switch once and while the switch is flashing (within 2 seconds *) press it again.
    * Settings can be changed at [Delay] on the [Switch] dialog.
  2. Check the settings at [Interlock] on the [Switch] dialog.

 

V9series|Pressing the reset switch does not clear history data. It is possible to clear history data by using PLC device memory.
In this case, set (ON) the reset bit of the control device memory for the alarm server.
For more information on the control device memory, click here.

Was this page helpful?

Please cooperate with the questionnaire to make it better.

  • Back to FAQ top

FAQ by product

  • V10/V9 series

  • V8/TS2060 series

  • TELLUS and V-Server

Most searched FAQs

  • Communication error "Error code received"
  • I want to search where these buttons are used:
    - Screen Change-over buttons
    - Overlap Control buttons
  • Communication Error "Timeout"
  • "The port cannot be opened."
  • What PLC models can be connected?
To page top
  • ≫ 產品諮詢
  • ≫ 營業銷售諮詢
  • ≫ 索取産品目錄
  • ≫ 支援RoHS指令

MONITOUCH

LINE UP
  • X1 SERIES
  • V10 SERIES
  • V9 SERIES
  • TECHNOSHOT
  • Web Machine Interface
  • Smart Editor
  • V-SFT
  • TELLUS and V-Server
服務中心 ≫
  • 下載
  • 諮詢
  • 推薦外圍設備
FAQ(常見問題) ≫
  • FAQ concerning MONITOUCH
代理商 ≫
  • Overseas distributors
  • ≫ Privacy Policy
Copyright©2013 Hakko Electronics Co., Ltd. All Right Reserved