Fuji Electric Co.,LTD
Global
Hakko Electronics (Taiwan)
Select Region
  • Global
  • Europe
  • Japan
  • China
  • Asia
    • Taiwan
    • Korea
Print
Font Size
  • Small
  • Medium
  • Large
  • 首頁
  • HMI
  • 公司簡介
  • ≫ 產品情報
  • ≫ 服務中心
  • ≫ FAQ(常見問題)
  • ≫ 代理商
  1. 首頁 >
  2. 產品情報
V10/V9 series Error HKFAQ000309

date: 2024/8/26

"Screen No. Error"

This error occurs when using a V8 compatible setting (*) on a V10/V9 series unit.

At the start of communication, the V10/V9 series initially displays the screen corresponding to the value specified for "n+2" in [Read Area].
"Screen No. Error" is displayed when the screen number entered for "n+2" in [Read Area] does not exist in the screen program.

   

* Procedure for checking V8 compatible settings:
- [Read/Write Area] is displayed at [System Setting] → [Hardware Setting] in V-SFT.

 

Solution 1

Check the value of "n+2" in [Read Area] and change it to the value of an existing screen number.
If the device memory of [Read Area] is unknown, check the following locations.
The screen number value can be checked in V-SFT and in Local mode on the V10/V9 series unit.

  

Locations to check

Checking in V-SFT

- [System Setting] → [Hardware Setting] → [Read/Write Area] → [Read Area] in V-SFT
   

Example) In the above screenshot, since the value of "n+2" in [Read Area] is "D00002", check the value of "D00002" on the PLC and change it to the value of an existing screen number if necessary.

* If the [GD-80 Compatible Read/Write Area] checkbox is selected in the [GD-80 Compatible] tab window, check the lower 8 bits of the device memory for "n+1" in [Read Area].

 

Checking in Local mode on the V10/V9 series unit

- Local mode → [System Information] → [Screen Data Information]
  Screen Command Memory (= "n+2" in [Read Area])
  

 * For more information on how to change to Local mode, click here.

 

If "Screen No. Error" is displayed when the emulator starts

Double-click the value of "n+2" in [Read Area] displayed in the [System] window of the simulator and change it to the value of an existing screen number.
Next, press the [Retry] switch on the emulator.

 

Solution 2

Set the initial screen.

* For V9, available with V-SFT Ver. 6.1.1.0 or later and V9 program Ver. 2.300 or later.

  

Setting location

[System Setting] → [Hardware Setting] → [Read/Write Area] → [Read Area] in V-SFT
Select the [Initial Screen] checkbox and set the initial screen number.

 

Was this page helpful?

Please cooperate with the questionnaire to make it better.

Related questions(FAQ)

  • The V series does not switch from the RUN screen to Local mode.
  • How to change-over the screen according to a PLC (external) command
  • Back to FAQ top

FAQ by product

  • V10/V9 series

  • V8/TS2060 series

  • TELLUS and V-Server

Most searched FAQs

  • Communication error "Error code received"
  • I want to search where these buttons are used:
    - Screen Change-over buttons
    - Overlap Control buttons
  • Communication Error "Timeout"
  • "The port cannot be opened."
  • What PLC models can be connected?
To page top
  • ≫ 產品諮詢
  • ≫ 營業銷售諮詢
  • ≫ 索取産品目錄
  • ≫ 支援RoHS指令

MONITOUCH

LINE UP
  • X1 SERIES
  • V10 SERIES
  • V9 SERIES
  • TECHNOSHOT
  • Web Machine Interface
  • Smart Editor
  • V-SFT
  • TELLUS and V-Server
服務中心 ≫
  • 下載
  • 諮詢
  • 推薦外圍設備
FAQ(常見問題) ≫
  • FAQ concerning MONITOUCH
代理商 ≫
  • Overseas distributors
  • ≫ Privacy Policy
Copyright©2013 Hakko Electronics Co., Ltd. All Right Reserved