date: 2021/2/17
How to save logging data even after turning off power to the V series
Set "SRAM" as the saving destination of logging data.
With [SRAM] selected, backup power is supplied from the battery attached to the MONITOUCH when the power is OFF.
- Click [System Setting] -> [Logging Server] and then select a logging block number.
 Click [Output Destination] -> [Detail Settings] and set [Device Type] as "SRAM".
 (Default setting: SRAM)
 
- Transfer the screen data.
- "Error : 163 (SRAM : 0)" or "161 (SRAM : 0)" is displayed. 
 The V series SRAM must be formatted.
 Switch the V series to Local mode, and press [SRAM Setting] -> [Format] -> [Execute].
 For more information, click here.
 * Click [System Setting] -> [Unit Setting] -> [SRAM/Clock] and check [SRAM Auto Format] to automatically format the SRAM. 
 