V10/V9 series Questions about HKFAQ000078

date: 2024/9/25

How to check the communication condition between the temperature controller and the V series

The temperature controller condition is output to the system device memory of the V series.
Check the following device memory addresses for each station number.

  1. Click [System Setting] -> [Hardware Setting] and display a [PLCx Properties] dialog on the V-SFT editor. Then select [Disconnect] for [Comm. Error Handling].
    How to check the communication condition between the temperature controller and the V series

     

  2. The communication results with each station are stored in the system device memory as below.
    Assign system device memory addresses to numerical data display parts for monitoring.
    System device memory: $Pn: 100 - 355 (n: PLC1 - 8) ..... Station No. 0 - 255

    Example: When a temperature controller is registered to PLC2 as station No. 10, monitor $P2: 110.

 

Error details

Code (HEX)

Description

 0000H  Normal
 FFFFH  Timeout
 8001H  Check code error
 8002H  Data error
 800BH

 Error code received from the
 connected device *

* The received code can be acquired at $Pn: 508 to 511. For more information, click here.

 

Other error codes are shown below:
How to check the communication condition between the temperature controller and the V series

 

Error

Details

Solution

Timeout Although a request to send is given, no answer is returned within the specified time. Take actions 1, 2, and 3.
Check code The response check code is not correct. Take actions 1 and 3.
Data error The received code is invalid. Take actions 1, 2, and 3.
Error code received An error is occurring at the connected device. Refer to the PLC manual.
Buffer full The buffer of the V series is full. Contact your HAKKO representative.
Parity A parity check error has occurred. Take actions 2 and 3.
Overrun After one character is received, the next character is received before internal processing is completed. Take actions 1 and 3.
Framing Although the stop bit must be "1", it is detected as "0". Take actions 1, 2 and 3.
Break detection The SD of the connected device remains at the low level. Check connection to the SD/RD of the connected device.

 

What to do:

  1. Check that communication settings of the V series match those of the connected device.
  2. Check the cable connection.
  3. Data may be disrupted because of noise. Provide protection against noise.

Was this page helpful?

Please cooperate with the questionnaire to make it better.

Related questions(FAQ)

  • How to read or write data between the temperature controller/inverter and the PLC device memory or internal device memory at regular intervals
  • Back to FAQ top

FAQ by product

  • V10/V9 series

  • V8/TS2060 series

  • TELLUS and V-Server

Most searched FAQs

  • Communication error "Error code received"
  • I want to search where these buttons are used:
    - Screen Change-over buttons
    - Overlap Control buttons
  • Communication Error "Timeout"
  • "The port cannot be opened."
  • What PLC models can be connected?
To page top
  • ≫ 產品諮詢
  • ≫ 營業銷售諮詢
  • ≫ 索取産品目錄
  • ≫ 支援RoHS指令

MONITOUCH

LINE UP
  • X1 SERIES
  • V10 SERIES
  • V9 SERIES
  • TECHNOSHOT
  • Web Machine Interface
  • Smart Editor
  • V-SFT
  • TELLUS and V-Server
服務中心 ≫
  • 下載
  • 諮詢
  • 推薦外圍設備
FAQ(常見問題) ≫
  • FAQ concerning MONITOUCH
代理商 ≫
  • Overseas distributors
  • ≫ Privacy Policy
Copyright©2013 Hakko Electronics Co., Ltd. All Right Reserved