V10/V9 series Error HKFAQ000013

date: 2018/12/17

The PLC device memory address for a part is garbled as "??" or is "blank".

 

<Causes>

  1. When the PLC model setting is changed, it is replaced with device "??".
  2. PLC2 - 8 are set as "not used" (delete).
  3. Variable name cooperation is not accomplished with a PLC project file of Fuji Electric's MICREX-SX.

 

<Solutions>

  1. When changing the PLC model, display the [Device Conversion] dialog and change "??" to an existing device memory address under [After Change Start Device].

    Example: Change the PLC from Mitsubishi's QnU series CPU → Fuji Electric's MICREX-SX series CPU.
    (1)After the PLC model is changed, the "Execute device conversion?"
     message dialog will be displayed. Click [Yes].
    V9series|The_PLC_device_memory_address_for_a_part_is_garbled_as_??_or_is_blank.

    (2)Click the "??" device memory after conversion that corresponds to
     the "M"device memory before conversion.
    V9series|The_PLC_device_memory_address_for_a_part_is_garbled_as_??_or_is_blank

    (3) Set WM0 in the [Device Input] dialog, and click [OK].
    V9series|The_PLC_device_memory_address_for_a_part_is_garbled_as_??_or_is_blank
    "M" device memory is changed so that it will start from WM0.
    V9series|The_PLC_device_memory_address_for_a_part_is_garbled_as_??_or_is_blank

  2. Correct or delete all illegal device memory addresses.
    Illegal device memory addresses can be found by running an error check.

    Example: [Tool] → [Error Check]
    V9series|The_PLC_device_memory_address_for_a_part_is_garbled_as_??_or_is_blank

    Click the [Jump to Error Item] icon to jump to the error occurring position.
    Delete or modify the illegal device memory address.
    V9series|The_PLC_device_memory_address_for_a_part_is_garbled_as_??_or_is_blank

  3. Link up with the PLC project file.
    List of PLC models which require linkup (IEC mode only *)
    • MICREX-SX (T-link)
    • MICREX-SX (OPCN-1)
    • MICREX-SX (SX bus)
    • MICREX-SX SPH/SPB/SPM/SPE/SPF series
    • MICREX-SX SPH/SPB/SPM/SPE/SPF CPU
    • MICREX-SX (Ethernet)
      * The current mode setting can be viewed by selecting [MICREX-SX] → [Select Device].

V9series|The_PLC_device_memory_address_for_a_part_is_garbled_as_??_or_is_blank


(1) Select [MICREX-SX] → [Project] → [Option], and check [? Cooperating work].
V9series|The_PLC_device_memory_address_for_a_part_is_garbled_as_??_or_is_blank

(2) Select the PLC project file (extension ".mwt").
V9series|The_PLC_device_memory_address_for_a_part_is_garbled_as_??_or_is_blank

(3) Check that the correct PLC project file is displayed for [Path], and click [OK].
V9series|The_PLC_device_memory_address_for_a_part_is_garbled_as_??_or_is_blank
*Note the following points for the project name and pathname. If not, the file will not be linked correctly.

  • The following characters must not be used for the pathname.
    :, ., =, ;, <, >, [, ], /, ?, |, *, "
  • The following characters must not be used for the project name.
    ¥, :, ., =, ;, <, >, [, ], /, ?, |, *, "
  • The project name must not exceed 24 characters.
    (24 one-byte characters/12 two-byte characters, one-byte and two-byte characters can be used at the same time)
  • The project pathname (from the drive name to the project name) must not exceed 171 characters.

Was this page helpful?

Please cooperate with the questionnaire to make it better.

  • Back to FAQ top

FAQ by product

  • V10/V9 series

  • V8/TS2060 series

  • TELLUS and V-Server

Most searched FAQs

  • Communication error "Error code received"
  • I want to search where these buttons are used:
    - Screen Change-over buttons
    - Overlap Control buttons
  • Communication Error "Timeout"
  • "The port cannot be opened."
  • What PLC models can be connected?
To page top
  • » Inquiries about products
  • » Inquiries about sales
  • » Request for catalogs
  • » Compliance with the RoHS

MONITOUCH

LINE UP
  • X1 SERIES
  • V10 SERIES
  • V9 SERIES
  • TECHNOSHOT
  • Web Machine Interface
  • Smart Editor
  • V-SFT
  • TELLUS and V-Server
Support »
  • Download
  • Inquiries
  • Recommended peripheral equipment
FAQ »
  • FAQ concerning MONITOUCH
Distributors »
  • Overseas distributors
  • » Privacy Policy
Copyright©2013 Hakko Electronics Co., Ltd. All Right Reserved