V8/TS2060 series Operation Troubles HKFAQ000136

date: 2021/7/14

The lamp lights up even though the bit in the lamp device memory is not ON.

 

<Cause>

The lamp device memory is used redundantly.

 

<Solution>

Check if the same address as the lamp device memory is used in the screen data or in the PLC program.
Depending on the value set for [No. of Patterns], the number of device memory addresses used will vary. Check the availability of these device memory addresses.

 

Example: When five lamps (No. of Patterns: 3) are configured consecutively from lamp device memory M0000 (bit):

V-SFT Ver.6


V-SFT Ver.5
V8series|The lamp lights up even though the bit in the lamp memory is not ON.

 OFF     ON     P3
V8series|The lamp lights up even though the bit in the lamp memory is not ON.
 
     Wrong                 Correct
V8series|The lamp lights up even though the bit in the lamp memory is not ON.
When "3" is set for [No. of Patterns], 2 bits are used.

L1 (M0000/M0001)
L2 (M0002/M0003)
L3 (M0004/M0005)
L4 (M0006/M0007)
L5 (M0008/M0009)

As the number of patterns is increased, the number of bits used is also increased.

 

L1 lamp example:

OFF display  M0000 : OFF, M0001 : OFF
ON display   M0000 : ON, M0001 : OFF
P3 display*  M0000 : OFF, M0001 : ON

* Since the higher bits have priority, P3 display is shown when M0001 is ON.

Was this page helpful?

Please cooperate with the questionnaire to make it better.

  • Back to FAQ top

FAQ by product

  • V10/V9 series

  • V8/TS2060 series

  • TELLUS and V-Server

Most searched FAQs

  • Communication error "Error code received"
  • I want to search where these buttons are used:
    - Screen Change-over buttons
    - Overlap Control buttons
  • Communication Error "Timeout"
  • "The port cannot be opened."
  • What PLC models can be connected?
To page top
  • » Inquiries about products
  • » Inquiries about sales
  • » Request for catalogs
  • » Compliance with the RoHS

MONITOUCH

LINE UP
  • X1 SERIES
  • V10 SERIES
  • V9 SERIES
  • TECHNOSHOT
  • Web Machine Interface
  • Smart Editor
  • V-SFT
  • TELLUS and V-Server
Support »
  • Download
  • Inquiries
  • Recommended peripheral equipment
FAQ »
  • FAQ concerning MONITOUCH
Distributors »
  • Overseas distributors
  • » Privacy Policy
Copyright©2013 Hakko Electronics Co., Ltd. All Right Reserved