Fuji Electric Co.,LTD
Global
Hakko Electronics (HMI)
Select Region
  • Global
  • Europe
  • Japan
  • China
  • Asia
    • Taiwan
    • Korea
Print
Font Size
  • Small
  • Medium
  • Large
  • Home
  • HMI
  • Company profile
  • » Products
  • » Support
  • » FAQ
  • » Distributors
  1. Home >
  2. FAQ
TELLUS and V-Server Operation Troubles HKFAQ000213

date: 2022/10/7

I click a button on the screen in the TELLUS-Remote mode, but the data is not written to the MONITOUCH or PLC.

Check the output device and set it correctly.


For system device ($s/$T):

It is not possible to write any value from remote screen to the monitored device.


PLC1-PLC8 device or I/O device:

Reset the write-protect setting.
The write-protect setting is made on V-Server. 

 

User device ($u) or memory card device:

Reset the write-protect setting.
Also reset the memory protect setting from [Network table setting] > [Device protect] option in V-SFT.

 

Device types available for remote mode

Device Read Write Remarks

PLC1-PLC8 device

I/O device

Y Y Writing is not allowed if the read-only setting is specified for the PLC
User device $u/$L/$LD Y Y  
$T N N Remote PC's internal memory
System device $s N N Remote PC's internal memory
Memory card memory Y Y  
Temperature controller memroy Y Y Writing is not allowed if the read-only setting is specified for the PLC

 

V-Server: write protect setting

  1. Select the monitored device to which writing is impossible from V-Server.
  2. From the [Edit] menu, select [Remote Monitor Setting].
    The [Remote Monitor Setting] dialog box is displayed.
  3. Uncheck [Write Protect] box.

     

Write protect setting on the monitored device

For V series
  1. Start V-SFT and open a screen program.
  2. Go to [System Setting]>[Ethernet Communication]>[Local IP address].
  3. Uncheck [Device Protect].


*When [Select IP Address from Network Table] is checked, go to [System Setting] > [Ethernet Communication] > [Network Table] to uncheck the Device Protect option.



For TELLUS
  1. Open the [Option] dialog box.
  2. Click the [Detail Setting] button under [Ethernet].
    The [Ethernet Detail Setting] dialog box is displayed.
  3. Clear the checkmarks for [Memory Protect].



Was this page helpful?

Please cooperate with the questionnaire to make it better.

  • Back to FAQ top

FAQ by product

  • V10/V9 series

  • V8/TS2060 series

  • TELLUS and V-Server

Most searched FAQs

  • Communication error "Error code received"
  • I want to search where these buttons are used:
    - Screen Change-over buttons
    - Overlap Control buttons
  • Communication Error "Timeout"
  • "The port cannot be opened."
  • What PLC models can be connected?
To page top
  • » Inquiries about products
  • » Inquiries about sales
  • » Request for catalogs
  • » Compliance with the RoHS

MONITOUCH

LINE UP
  • X1 SERIES
  • V10 SERIES
  • V9 SERIES
  • TECHNOSHOT
  • Web Machine Interface
  • Smart Editor
  • V-SFT
  • TELLUS and V-Server
Support »
  • Download
  • Inquiries
  • Recommended peripheral equipment
FAQ »
  • FAQ concerning MONITOUCH
Distributors »
  • Overseas distributors
  • » Privacy Policy
Copyright©2013 Hakko Electronics Co., Ltd. All Right Reserved