V9 series Error HKFAQ000003

date: 2017/9/13

Communication Error "Simulator: Timeout", "Simulator: Link down"

This error is displayed on the V series when simulator communication is not established correctly between the V series and the PC.

 

[Communication with a PLC]

The communication setting is configured not with a PLC but with the simulator.
Configure settings for communication with a PLC in Local mode on the V9 series, or transfer screen data that does not require a simulator.

 

<Solutions>

Setting change procedure in Local mode

  1. Switch to Local mode on the V9 series.
  2. Press [Simulator Setting] in the menu icons to display the simulator settings. Select [Not Use (Actual Machine)] and press the [Apply] switch.V9series|CommunicationErrorSimulator:TimeoutSimulat
  3.  Press [RUN] in the menu icons to switch to the RUN screen.

 

Configuration procedure for not using the simulator from the V-SFT editor

  1. Click [Transfer] -> [Download] to display the [Transfer] dialog.
  2. Uncheck [Use Simulator], and click [PC->] to transfer the screen data again.
    V9series|CommunicationErrorSimulator:TimeoutSimulat

 

 

[Communication with simulator]

The simulator is not running properly or communication is not established between the PC and the V series.

 

<Solutions>

  1. Switch to Local mode and select [Simulator Setting] -> [Use] and press the [Apply] switch.V9series|CommunicationErrorSimulator:TimeoutSimulat
    * When connecting the V9 series with a PC via Ethernet, the IP address of the PC must be specified at [Simulator Information]. 

  2. Press [RUN] in the menu icons to switch to the RUN screen.

  3. Click [Transfer] -> [Simulator] on the V-SFT editor to start the simulator.V9series|CommunicationErrorSimulator:TimeoutSimulat

  4. The simulator starts up. Communication with the V9 series will start at the same time. Addresses related to the screen data currently open on the editor will be displayed on the simulator automatically.

V9series|CommunicationErrorSimulator:TimeoutSimulat

 

When communication is not possible:

Configure settings for communication between the PC and the V series from the [File] menu. For more information, refer to "How to check the operation of screens without connecting to a PLC."

V9series|CommunicationErrorSimulator:TimeoutSimulat

Was this page helpful?

Please cooperate with the questionnaire to make it better.

Related questions(FAQ)

  • How to check the operation of screens without connecting to a PLC
  • The V series does not switch from the RUN screen to Local mode.
  • Back to FAQ top

FAQ by product

  • V9 series

  • V8 series

  • TELLUS and V-Server

Most searched FAQs

  • What PLC models can be connected?
  • Communication error "Error code received"
  • Communication Error "Timeout"
  • How to save sampling data even after turning off the TS/V series
  • "The port cannot be opened."
To page top
  • » Inquiries about products
  • » Inquiries about sales
  • » Request for catalogs
  • » Compliance with the RoHS

MONITOUCH

LINE UP
  • X1 SERIES
  • V9 SERIES
  • TECHNOSHOT
  • Web Machine Interface
  • V-SFT
  • TELLUS and V-Server
Support »
  • Download
  • Inquiries
  • Recommended peripheral equipment
FAQ »
  • FAQ concerning MONITOUCH
Distributors »
  • Overseas distributors
  • » Privacy Policy
Copyright©2013 Hakko Electronics Co., Ltd. All Right Reserved