V8/TS2060 series Operation Troubles HKFAQ000134

date: 2021/8/31

Pressing a switch does not activate anything.

 

<Causes>

  1. Interlock is set for the switch.
  2. ON delay is set for the switch. (TS/V8 only)
  3. Touch switch position is deviated.
  4. When the screen change switch (Function: Screen) is used, the "screen internal switching" bit is ON so screen switching is disabled.

 

<Solutions>

  1. Display the [Switch] dialog → [Other Settings] → [Interlock] and check if [Use interlock] is checked. If checked, satisfy the conditions set for interlock.

     

    Example: Turn ON bit 0 of $u100 to enable switching.


    * When you use V-SFT Ver.5, check the [Switch] dialog → [Interlock] tab.
    V8series|Pressing a switch does not activate anything.

  2. Display the [Switch] dialog → [Other Settings] → [Delay] and check if [ON delay] is checked. If checked, satisfy the conditions set for ON delay.

    Example: ON after 1 second (10 x 100 msec)


    * When you use V-SFT Ver.5, check the [Switch] dialog → [Delay] tab.



  3. Check if touch switch position is deviated. If deviated, correct. For more information, refer to following FAQ.

    "HKFAQ000128    Pressing the touch switch activates nothing or activates a position that deviates from the switch".

     

  4. Check bit 13 (screen internal switching) of Read area "n + 1" If ON, turn it OFF.

    For details about how to check Read area, click here.

Was this page helpful?

Please cooperate with the questionnaire to make it better.

Related questions(FAQ)

  • Pressing the touch switch activates nothing or activates a position that deviates from the switch.
  • Back to FAQ top

FAQ by product

  • V10/V9 series

  • V8/TS2060 series

  • TELLUS and V-Server

Most searched FAQs

  • Communication error "Error code received"
  • I want to search where these buttons are used:
    - Screen Change-over buttons
    - Overlap Control buttons
  • Communication Error "Timeout"
  • "The port cannot be opened."
  • What PLC models can be connected?
To page top
  • » Inquiries about products
  • » Inquiries about sales
  • » Request for catalogs
  • » Compliance with the RoHS

MONITOUCH

LINE UP
  • X1 SERIES
  • V10 SERIES
  • V9 SERIES
  • TECHNOSHOT
  • Web Machine Interface
  • Smart Editor
  • V-SFT
  • TELLUS and V-Server
Support »
  • Download
  • Inquiries
  • Recommended peripheral equipment
FAQ »
  • FAQ concerning MONITOUCH
Distributors »
  • Overseas distributors
  • » Privacy Policy
Copyright©2013 Hakko Electronics Co., Ltd. All Right Reserved