V8/TS2060 series Operation Troubles HKFAQ000131

date: 2021/8/31

The screen is not switched according to the command from the PLC (external).

 The causes are listed below.

<Causes>

  1. The screen number to display is not specified in read area "n + 2".
  2. The specified screen number is the same as the previous screen number.

 

<Solutions>

  1. Check the value specified in read area "n + 2".
    The value must be specified in the data format (DEC/BCD) as set in the screen data.
    The set data format can be viewed in the following location.

      * For details about how to check Read area, click here.

    V8/TS series
    Setting location: V-SFT-6 editor [System Setting] → [Hardware Setting] →
                              [PLCx Properties]→ [Communication Setting] → [Code]

     

    V7 series
    Setting location: V-SFT-5 editor [System Setting] → [PLC Communication] →
                              [Communication Parameter] → [Detail] → [Code]

     

  2. Bit 14 (screen forced switching) of read area "n + 1" must be OFF → ON (leading edge).

Example: Read area "n + 2" (D2)

Step a: Change to screen No. 5 according to read area "n + 2"
Step b: Change to screen No. 2 with an internal switch
Step c: Change to the same screen number as step a (screen No. 5) according to read area "n + 2"

In this case, however, the same value is stored in read area "n + 2" so the command is not valid.
In such a case, it is possible to forcibly switch the screen to the screen number contained in read area "n + 2" at the leading edge [0 → 1] of bit 14 of read area "n + 1" (D1).

V8series|The screen is not switched according to the command from the PLC (external).

Was this page helpful?

Please cooperate with the questionnaire to make it better.

Related questions(FAQ)

  • How to change-over the screen according to a PLC (external) command
  • Back to FAQ top

FAQ by product

  • V10/V9 series

  • V8/TS2060 series

  • TELLUS and V-Server

Most searched FAQs

  • Communication error "Error code received"
  • I want to search where these buttons are used:
    - Screen Change-over buttons
    - Overlap Control buttons
  • Communication Error "Timeout"
  • "The port cannot be opened."
  • What PLC models can be connected?
To page top
  • » Inquiries about products
  • » Inquiries about sales
  • » Request for catalogs
  • » Compliance with the RoHS

MONITOUCH

LINE UP
  • X1 SERIES
  • V10 SERIES
  • V9 SERIES
  • TECHNOSHOT
  • Web Machine Interface
  • Smart Editor
  • V-SFT
  • TELLUS and V-Server
Support »
  • Download
  • Inquiries
  • Recommended peripheral equipment
FAQ »
  • FAQ concerning MONITOUCH
Distributors »
  • Overseas distributors
  • » Privacy Policy
Copyright©2013 Hakko Electronics Co., Ltd. All Right Reserved