V10/V9 series Error HKFAQ000001

date: 2024/11/5

Communication Error "Timeout"

This error is displayed when the V series does not receive an answer from a connected device (PLC, temperature controller, etc.) within the predetermined time after issuing a request to send.

 

[In cases where the error occurs before communication]

<Cause>

  1. The communication cable is not connected correctly or is disconnected.
  2. Communication settings on the V series do not match those of the connected device.

 

<Solution>

  1. Check the wiring and continuity of the cable.
  2. Check that the selection of [Maker] and [Series] on the V series is correct and that the communication settings including baud rate, data length, stop bit, and parity are the same between the connected device and the V series.

    Setting location: V-SFT editor [System Setting] -> [Hardware Setting]



    * Communication settings including signal level, baud rate, data length, stop bit, and parity can be configured in Local mode on the V series.

    Setting location: V series [Local] -> [Communication Setting]
    V9series|Communication


    Changes made on the local screen have priority over the settings made in the screen program.
    To restore original setting in the screen program, press [Restore Screen Data Setting] button then press [Reset All].
    * Restoring the settting will clear all the changes made on the local screen.



 

[In cases where the error occurs during normal communication]

<Cause>

Data may be disrupted because of noise.

 

<Solution>

Provide protection against noise.

Was this page helpful?

Please cooperate with the questionnaire to make it better.

Related questions(FAQ)

  • How to change communication setting such as [Signal Level] and [Baud Rate]
  • Back to FAQ top

FAQ by product

  • V10/V9 series

  • V8/TS2060 series

  • TELLUS and V-Server

Most searched FAQs

  • Communication error "Error code received"
  • I want to search where these buttons are used:
    - Screen Change-over buttons
    - Overlap Control buttons
  • Communication Error "Timeout"
  • "The port cannot be opened."
  • What PLC models can be connected?
To page top
  • » 제품에 관한 문의
  • » 영업 판매 문의
  • » 카탈로그 청구
  • » RoHS 지령에 대응

MONITOUCH

라인업
  • X1 SERIES
  • V10 SERIES
  • V9 SERIES
  • TECHNOSHOT
  • Web Machine Interface
  • Smart Editor
  • V-SFT
  • TELLUS and V-Server
서포트 »
  • 다운로드
  • 문의
  • 추천 주변기기
FAQ »
  • FAQ concerning MONITOUCH
대리점 »
  • Overseas distributors
  • » Privacy Policy
Copyright©2013 Hakko Electronics Co., Ltd. All Right Reserved