V8/TS2060 series Error HKFAQ000111

date: 2021/7/13

"Screen No. Error"

At the start of communication, the V8/TS series initially displays the screen corresponding to the value specified for "n+2" in [Read Area].
"Screen No. Error" is displayed when the screen number entered for "n+2" in [Read Area] does not exist in the screen program.

 

 

Check the value of "n+2" in [Read Area] and change it to the value of an existing screen number.
If the device memory of [Read Area] is unknown, check the following locations.

 

V8/TS series
Check position: V-SFT-6 editor [System Setting] → [Hardware Setting] →
                         [Read/Write Area] → [Read Area]

Example) In the above screenshot, since the value of "n+2" in [Read Area] is "D00002", check the value of "D00002" on the PLC and change it to the value of an existing screen number if necessary.

* If the [GD-80 Compatible Read/Write Area] checkbox is selected in the
   [GD-80 Compatible] tab window, check the lower 8 bits of the device memory
   for "n+1" in [Read Area].

 

V7 series
Check position: V-SFT-5 editor [System Setting] → [PLC Communication] →
                         [Communication Parameter] → [Main 1]

Example) In the above screenshot, since the value of "n+2" in [Read Area] is "D00002", check the value of "D00002" on the PLC and change it to the value of an existing screen number if necessary.

* If the [GD-80 Compatible Read/Write Area] checkbox is selected, check the
   lower 8 bits of the device memory for "n+1" in [Read Area].

 

If "Screen No. Error" is displayed when the emulator starts

Double-click the value of "n+2" in [Read Area] displayed in the [System] window of the simulator and change it to the value of an existing screen number.

Was this page helpful?

Please cooperate with the questionnaire to make it better.

Related questions(FAQ)

  • The screen is not switched according to the command from the PLC (external).
  • Back to FAQ top

FAQ by product

  • V10/V9 series

  • V8/TS2060 series

  • TELLUS and V-Server

Most searched FAQs

  • Communication error "Error code received"
  • I want to search where these buttons are used:
    - Screen Change-over buttons
    - Overlap Control buttons
  • Communication Error "Timeout"
  • "The port cannot be opened."
  • What PLC models can be connected?
To page top
  • » 제품에 관한 문의
  • » 영업 판매 문의
  • » 카탈로그 청구
  • » RoHS 지령에 대응

MONITOUCH

라인업
  • X1 SERIES
  • V10 SERIES
  • V9 SERIES
  • TECHNOSHOT
  • Web Machine Interface
  • Smart Editor
  • V-SFT
  • TELLUS and V-Server
서포트 »
  • 다운로드
  • 문의
  • 추천 주변기기
FAQ »
  • FAQ concerning MONITOUCH
대리점 »
  • Overseas distributors
  • » Privacy Policy
Copyright©2013 Hakko Electronics Co., Ltd. All Right Reserved