V8/TS2060 series Error HKFAQ000118

date: 2021/7/28

"Battery voltage drop", "Brownout of Battery", "Battery changeover required", "Battery not set"

This error is displayed on the Main Menu screen when a battery problem has occurred to the V/TS series.

 

In the case of "Battery voltage drop", "Brownout of Battery", "Battery changeover required"

<Cause>

The battery voltage has dropped.

 

<Solution>

Replace the battery with a new one.

  • V8/V7/V606e series
       Battery type: V7-BT
  • TS2060 series
       Battery type: TS-BT(CR2032W/CR2032X)
  • TS1000S series
       Battery type: CR2032

 

V8series|Battery not set,Battery voltage drop How to check the battery condition in the RUN mode The battery condition is output to the internal device memory $s167 of the V/TS2060/TS1000S .
A battery can last for about five years (*1) from the date of purchase. Even if the battery voltage drops (bit 4: ON) before the five years (*1) elapse, replace the battery immediately. (*2)

V8series|Battery not set, Battery voltage drop
(With the TS2060/TS1000S/V606e, "1: Battery voltage drop or no battery", "2" not provided)

*1 TS1000S:About three years
*2 When checking the battery condition on the PLC side, use the event timer macro to transfer the information to the PLC memory. For more information, click here.

 

 

In the case of "Battery not set" (V8/V7 only)

 

<Cause>

The battery is not connected.

 

<Solutions>

  • Open the battery holder cover at the backside of the MONITOUCH, and connect the battery cable.
    (At the time of delivery from the factory: Not connected)
  • Replace the battery with a new one.
    Battery type: V7-BT (V8/V7/V606e series)

 

 * For the procedure of checking the battery condition in the RUN mode, see above.

Was this page helpful?

Please cooperate with the questionnaire to make it better.

Related questions(FAQ)

  • How to indicate battery trouble of the V/TS series on the PLC side
  • Back to FAQ top

FAQ by product

  • V10/V9 series

  • V8/TS2060 series

  • TELLUS and V-Server

Most searched FAQs

  • Communication error "Error code received"
  • I want to search where these buttons are used:
    - Screen Change-over buttons
    - Overlap Control buttons
  • Communication Error "Timeout"
  • "The port cannot be opened."
  • What PLC models can be connected?
To page top
  • » 제품에 관한 문의
  • » 영업 판매 문의
  • » 카탈로그 청구
  • » RoHS 지령에 대응

MONITOUCH

라인업
  • X1 SERIES
  • V10 SERIES
  • V9 SERIES
  • TECHNOSHOT
  • Web Machine Interface
  • Smart Editor
  • V-SFT
  • TELLUS and V-Server
서포트 »
  • 다운로드
  • 문의
  • 추천 주변기기
FAQ »
  • FAQ concerning MONITOUCH
대리점 »
  • Overseas distributors
  • » Privacy Policy
Copyright©2013 Hakko Electronics Co., Ltd. All Right Reserved