V8/TS2060 series Error HKFAQ000121

date: 2021/7/28

"The size is too large to communicate."

This error may be displayed on the configuration software V-SFT when data is transferred.
Possible causes and solutions are given below.

 

<Causes>

  1. The size of the screen data to transfer may have exceeded the capacity available with the TS/V series.

  2. With V606/V606i/V609E:
    These products do not support a data transfer rate of 115 Kbps.
    The data transfer rate may be set to 115 Kbps.

<Solutions>

  1. Select [Tool] → [List of Memory Use] on the V-SFT editor and check the screen data size.


    TS/V8 series
    If the capacity is exceeded, make the screen data size smaller.
    For example, store data of screens, messages, patterns, etc. on a CF card to reduce the screen data size.
     Setting location: V-SFT Ver. 6 editor [System Setting] → [Other] → [Storage Setting]

     

    V7 series
    If the capacity is exceeded, make the screen data size smaller.
    For example, store data of patterns on a CF card to reduce the screen data size.
     Setting location: V-SFT Ver. 5 editor [System Setting] → [CF Card Setting]

     

    V6 series
    If any font other than Japanese fonts is set, select "English" on the Main Menu screen.
     Setting location: V-SFT Ver. 5 editor [System Setting] → [Font Setting]

     

  2. Lower the transfer rate to 57600 bps or less, and transfer data again.

Was this page helpful?

Please cooperate with the questionnaire to make it better.

  • Back to FAQ top

FAQ by product

  • V10/V9 series

  • V8/TS2060 series

  • TELLUS and V-Server

Most searched FAQs

  • Communication error "Error code received"
  • I want to search where these buttons are used:
    - Screen Change-over buttons
    - Overlap Control buttons
  • Communication Error "Timeout"
  • "The port cannot be opened."
  • What PLC models can be connected?
To page top
  • » 제품에 관한 문의
  • » 영업 판매 문의
  • » 카탈로그 청구
  • » RoHS 지령에 대응

MONITOUCH

라인업
  • X1 SERIES
  • V10 SERIES
  • V9 SERIES
  • TECHNOSHOT
  • Web Machine Interface
  • Smart Editor
  • V-SFT
  • TELLUS and V-Server
서포트 »
  • 다운로드
  • 문의
  • 추천 주변기기
FAQ »
  • FAQ concerning MONITOUCH
대리점 »
  • Overseas distributors
  • » Privacy Policy
Copyright©2013 Hakko Electronics Co., Ltd. All Right Reserved