V8/TS2060 series Operation Troubles HKFAQ000130

date: 2021/7/7

MONITOUCH does not switch from the RUN screen to the Main Menu screen.

Press the [SYSTEM] switch, and when the switch menu is displayed press the [F1] (MODE) switch.

V8series|MONITOUCH does not switch from the RUN screen to the Main Menu screen.

 

[If the switch menu is not displayed when the [SYSTEM] switch is pressed]

<Cause>

The [SYSTEM] switch is disabled.

 

<Solution>

Press the following two switches at the same time for the change-over time (max. 30 seconds). The change-over time is set in the screen data.

 

Other than V806/TS2060/V706 series

[SYSTEM] switch and [F7] switch

 

V806/TS2060/V706 series

[SYSTEM] switch and [F5] switch

 

V8series|MONITOUCH does not switch from the RUN screen to the Main Menu screen. The change-over time setting can be viewed in the following location.
Setting location: V-SFT editor [System Setting] → [Unit Setting] → [System/Mode Switch] 

 

 

[If the switch menu is displayed but the Main Menu screen is not displayed]

<Causes>

  1. [Change-over Time] is set for the [F1] (MODE) switch.
  2. The [F1] (MODE) switch is disabled.

 

<Solutions>

  1. Press the [SYSTEM] switch to display the switch menu and hold down the [F1] (MODE) switch for the change-over time (max. 30 seconds). The change-over time is set in the screen data.

  2. Press the [SYSTEM] switch to display the switch menu and hold down the following two switches at the same time for the change-over time (max. 30 seconds). The change-over time is set in the screen data.

    Other than V806/TS2060/V706 series
    [F1] (MODE) switch and [F7] switch

    V806/TS2060/V706 series
    [F1] (MODE) switch and [F5] switch

 

V8series|MONITOUCH does not switch from the RUN screen to the Main Menu screen. The change-over time setting can be viewed in the following location.
Setting location: V-SFT editor [System Setting] → [Unit Setting] → [System/Mode Switch]

Was this page helpful?

Please cooperate with the questionnaire to make it better.

  • Back to FAQ top

FAQ by product

  • V10/V9 series

  • V8/TS2060 series

  • TELLUS and V-Server

Most searched FAQs

  • Communication error "Error code received"
  • I want to search where these buttons are used:
    - Screen Change-over buttons
    - Overlap Control buttons
  • Communication Error "Timeout"
  • "The port cannot be opened."
  • What PLC models can be connected?
To page top
  • » 제품에 관한 문의
  • » 영업 판매 문의
  • » 카탈로그 청구
  • » RoHS 지령에 대응

MONITOUCH

라인업
  • X1 SERIES
  • V10 SERIES
  • V9 SERIES
  • TECHNOSHOT
  • Web Machine Interface
  • Smart Editor
  • V-SFT
  • TELLUS and V-Server
서포트 »
  • 다운로드
  • 문의
  • 추천 주변기기
FAQ »
  • FAQ concerning MONITOUCH
대리점 »
  • Overseas distributors
  • » Privacy Policy
Copyright©2013 Hakko Electronics Co., Ltd. All Right Reserved