V8/TS2060 series Operation Troubles HKFAQ000133

date: 2021/8/2

When a screen with an overlap display is switched to another and is switched back, the overlap part disappears.

 

<Cause>

When displaying a normal overlap or call-overlap part according to the status of the corresponding bit in read area "n + 1", this is recognized only at the leading edge (OFF → ON).
If the screen is moved back while the bit remains ON, the overlap part will not be displayed.

 

<Solution>

The following four methods are available.

 

  1. To display the overlap part whenever the bit is ON, select [System Setting] → [Unit Setting] → [General Settings] and check [Display Overlap during bit ON].

     

  2. Stop using read area "n + 1", and check [Control Device] in [Status of Use] of the overlap setting dialog.
    Command memory Bit 0
     OFF: No display
     ON: Display
     Example: Control Device for normal overlap
     

      * When you use V-SFT Ver.5, check [Command Memory] in the [Detail] tab
         of the overlap setting dialog.
       V8series|When a screen with an overlap display is switched to another and is switched back, the overlap part disappears.

     

  3. Use a multi-overlap part and call it with an external command (using the control device memory).

     

  4. Use a global overlap part.

Was this page helpful?

Please cooperate with the questionnaire to make it better.

  • Back to FAQ top

FAQ by product

  • V10/V9 series

  • V8/TS2060 series

  • TELLUS and V-Server

Most searched FAQs

  • Communication error "Error code received"
  • I want to search where these buttons are used:
    - Screen Change-over buttons
    - Overlap Control buttons
  • Communication Error "Timeout"
  • "The port cannot be opened."
  • What PLC models can be connected?
To page top
  • » 제품에 관한 문의
  • » 영업 판매 문의
  • » 카탈로그 청구
  • » RoHS 지령에 대응

MONITOUCH

라인업
  • X1 SERIES
  • V10 SERIES
  • V9 SERIES
  • TECHNOSHOT
  • Web Machine Interface
  • Smart Editor
  • V-SFT
  • TELLUS and V-Server
서포트 »
  • 다운로드
  • 문의
  • 추천 주변기기
FAQ »
  • FAQ concerning MONITOUCH
대리점 »
  • Overseas distributors
  • » Privacy Policy
Copyright©2013 Hakko Electronics Co., Ltd. All Right Reserved