date: 2021/7/6
In the alarm tracking display, alarm data is not tracked for the specified number of times.
<Cause>
[Buffering Area Setting] → [Number of Data to Save] is small.
<Solution>
Increase the number set for [Number of Data to Save].
For alarm tracking and alarm logging, an occurrence is regarded as one bit operation, and a reset is also regarded as one bit operation.
Consequently, to keep one error bit change as historical data, "2" should be set at minimum.
V8/TS series
Setting location: [System Setting] → [Buffering Area Setting] → [Data Output Settings]
V7/V6 series
Setting location: [System Setting] → [Buffering Area Setting]