V8/TS2060 series Operation Troubles HKFAQ000152

date: 2021/7/8

The time and date is not displayed correctly.

The solutions vary depending on the screen data settings.
Check the following settings.

Setting location:
V-SFT editor [System Setting] → [Unit Setting] → [SRAM/Clock] → [Use Built-in Clock]

Checked ..... Clock built in the V/TS series used
Unchecked ..... Clock built in the PLC used

V8series|In the alarm tracking display, alarm data is not tracked for the specified number of times.

 

[[Use Built-in Clock] checked]

<Causes>

  1. No battery is set in MONITOUCH.
  2. The clock built in the V/TS series is not set to the correct date and time.

 

<Solutions>

  1. Set a battery in the battery holder in the back of the V/TS series.
  2. There are two methods for adjusting the clock of the V/TS series. Follow the steps below.

 

  • Method 1: Adjustment on the Main Menu screen
    In the case of the V8 series, click here.
    In the case of the TS2060, click here.
    In the case of the TS1000S, click here.
    In the case of the V7 series, click here.
  • Method 2: Adjustment using a macro command
    It is necessary to create a clock correction screen.
    V8/TS series ... "SET_SYS_CLND"
    V7 series ... "SET_CLND"
    For more information on macro commands, refer to the Macro Reference Manual.

 

[[Use Built-in Clock] unchecked]

The clock built in the PLC is used.

<Causes>

  1. No battery is set in the PLC.
  2. The clock built in the PLC is not set to the correct date and time.

 

<Solutions>

  1. Set batteries in the PLC.
  2. There are two methods for setting the date and time.

     

  • Method 1: Correction using the PLC software and bit 11 of read area "n"
    The PLC calendar memory can be corrected using the PLC software.
    Calendar data is read into the V/TS series when bit 11 of read area "n" turns ON (0 → 1).
    * For correction on the PLC, refer to the relevant PLC manual.

     

  • Method 2: Adjustment using a macro command
    The PLC calendar can be corrected using macro command "SET_CLND".

     

    Example: To correct 2013/1012 10:40:00 to 20:00:00:

    (1) Create a calendar setting screen.
    V8series|In the alarm tracking display, alarm data is not tracked for the specified number of times.
    Place the following parts on the screen.
     - Keypad
     - Numerical data display part
    [Function:Entry Target] ($u0 to $u5)
     - Switch ON macro "SET_CLND"
     - Time display or calendar

    (2) Input year, month, day, time, hour, minute, second in order using the keypad, and press the switch to execute the SET_CLND macro. The PLC calendar is rewritten.

    Set 2013/10/15 20:00:00.

    Year: $u0 = 2013
    Month: $u1 = 10
    Day: $u2 = 15
    Hour: $u3 = 20
    Minute: $u4 = 0
    Second: $u5 = 0

    V8series|In the alarm tracking display, alarm data is not tracked for the specified number of times.
    The PLC calendar is read into the V/TS series and the V/TS series calendar is also re-written.
    V8series|In the alarm tracking display, alarm data is not tracked for the specified number of times.
    * In the case of the V8/TS series, the following macro commands are used to correct the calendar data in PLC2 to PLC8.
     - PLC_CLND ... PLC calendar write
     - SET_SYS_CLND ... V/TS series calendar write
    For more information, refer to the Macro Reference Manual.

Was this page helpful?

Please cooperate with the questionnaire to make it better.

  • Back to FAQ top

FAQ by product

  • V10/V9 series

  • V8/TS2060 series

  • TELLUS and V-Server

Most searched FAQs

  • Communication error "Error code received"
  • I want to search where these buttons are used:
    - Screen Change-over buttons
    - Overlap Control buttons
  • Communication Error "Timeout"
  • "The port cannot be opened."
  • What PLC models can be connected?
To page top
  • » 제품에 관한 문의
  • » 영업 판매 문의
  • » 카탈로그 청구
  • » RoHS 지령에 대응

MONITOUCH

라인업
  • X1 SERIES
  • V10 SERIES
  • V9 SERIES
  • TECHNOSHOT
  • Web Machine Interface
  • Smart Editor
  • V-SFT
  • TELLUS and V-Server
서포트 »
  • 다운로드
  • 문의
  • 추천 주변기기
FAQ »
  • FAQ concerning MONITOUCH
대리점 »
  • Overseas distributors
  • » Privacy Policy
Copyright©2013 Hakko Electronics Co., Ltd. All Right Reserved