V8/TS2060 series Questions about HKFAQ000188

date: 2021/8/5

How to check the operation of screens without connecting to a PLC

Use the simulator.
The simulator allows you to verify screen operations without a PLC.
The simulator runs on a PC and simulates bit device ON/OFF action and word device data input.

Connection between PC and MONITOUCH

  • Serial connection
  • USB connection (V8/TS series, V706, V715 only)
  • Ethernet connection (V8 series/TS2060i only)

[Step]

  1. Select [Transfer] → [Download] on the V-SFT editor, check [Use Simulator], and transfer screen data.
    * In the case of V-SFT Ver.5, select [File] → [Transfer], and check [Use Simulator].


     
  2. In the case of the V8/TS series, configure the settings on the Simulator Setting screen.
    For information on the settings, click here.
    *These settings are not required in the case of the V7 series. Go to step 3.
    V8series|How to check the operation of screens without connecting to a PLC

     

  3. Click [Transfer] → [Simulate] on the V-SFT editor.

    * In the case of V-SFT Ver.5, click the [SIM] icon or click [View] → [View] → [Simulate]. 

  4. The [Simulator] window opens.
    Simulator communication will start when the simulator has been launched.
    During communication, [Communication] → [Start] is checked, and the [Communication] icon is depressed.
    V8series|How to check the operation of screens without connecting to a PLC     or V8series|How to check the operation of screens without connecting to a PLC

    Double-click on a cell under [Value] to display the [Write Memory] dialog.
    It is also possible to write values or to bit-write by clicking the ON/OFF icon.
    V8series|How to check the operation of screens without connecting to a PLC

 

V8series|How to check the operation of screens without connecting to a PLC

When connecting MONITOUCH to a PLC after operations are verified, configure as below.

  • Select [Real machine] on the Simulator Setting screen on MONITOUCH (V8/TS series only).
    or
  • Select [Transfer] → [Download] on the V-SFT editor, uncheck [Use Simulator] and transfer screen data again.

 

When communication is not successful:
If the simulator's communication settings are not correct, the V/TS series cannot communicate with a PC properly.
If not successful, click [Communication] → [End] on the simulator to abort communication. Be sure to select [File] → [Communication Setting] and check the settings.

 

<Serial communication>

Select [File] on the simulator, check that [Comm. through USB] and [Comm. through Ethernet] are not checked, and click [Communication Setting].
V8series|How to check the operation of screens without connecting to a PLC

Set the COM number for [Communication Port]. Set the same COM number as that on the PC.
V8series|How to check the operation of screens without connecting to a PLC

 

<USB communication>

Select [File] on the simulator and check [Comm. through USB].
V8series|How to check the operation of screens without connecting to a PLC

 

<Ethernet communication>

  1. Register the IP address of the PC on the Simulator Setting screen on MONITOUCH.
    V8series|How to check the operation of screens without connecting to a PLC

  2. Select [File] on the simulator, check that [Comm. through Ethernet] is checked, and click [Communication Setting].
    V8series|How to check the operation of screens without connecting to a PLC

    Set the port number.
    The default port No. is 8020.
    If changed, set the changed port number on the Simulator Setting screen on MONITOUCH.
    V8series|How to check the operation of screens without connecting to a PLC

    For information on the settings on MONITOUCH, click here.

Was this page helpful?

Please cooperate with the questionnaire to make it better.

  • Back to FAQ top

FAQ by product

  • V10/V9 series

  • V8/TS2060 series

  • TELLUS and V-Server

Most searched FAQs

  • Communication error "Error code received"
  • I want to search where these buttons are used:
    - Screen Change-over buttons
    - Overlap Control buttons
  • Communication Error "Timeout"
  • "The port cannot be opened."
  • What PLC models can be connected?
To page top
  • » 제품에 관한 문의
  • » 영업 판매 문의
  • » 카탈로그 청구
  • » RoHS 지령에 대응

MONITOUCH

라인업
  • X1 SERIES
  • V10 SERIES
  • V9 SERIES
  • TECHNOSHOT
  • Web Machine Interface
  • Smart Editor
  • V-SFT
  • TELLUS and V-Server
서포트 »
  • 다운로드
  • 문의
  • 추천 주변기기
FAQ »
  • FAQ concerning MONITOUCH
대리점 »
  • Overseas distributors
  • » Privacy Policy
Copyright©2013 Hakko Electronics Co., Ltd. All Right Reserved