TELLUS and V-Server Operation Troubles HKFAQ000210

date: 2022/9/12

<TELLUS-HMI> Connection with MITSUBISHI Q series via Ethernet unit cannot be established.

Check the setting below.

 

Screen program settings

For V-SFT-6: [System Setting] > [Hardware Setting]

For V-SFT-5: [System Setting] > [Device Connection Setting]

  • Select appropriate setting from [Select PLC Type]:

QnU series CPU with built-in LAN port: [QnU series (built-in Ethernet)]

Q series with an Ethernet unit: [QnH(Q) series (Ethernet)]

  • [Device Connection Setting] > [PLC table] and specify PLC's IP addres and a port number

 

PLC settings

Built-in LAN port on the CPU

Set [PC parameter] in PLC programming software.

 

 

Ethernet unit

Set [Network parameters] in the PLC programming software.

Network parameters setting

Network type: Ethernet

 

Ethernet oprations

Set an IP address and other settings.

 

Port No. setting

There are two different ways to set a port number. [Automatic open UDP port] is used for communications in a case where any Ethernet unit is available (models available are not designated).
[Open setting] is used in a case where communications are conducted only with the unit connected via Ethernet.

  • Automatic open UDP port
    The port number can be changed on the PLC programming software. 5000 (DEC) is set as default.

 

  • Open setting
    [Network parameters setting] > [Open settings]

Protocol UDP
Fixed buffer Send or Receive
Fixed buffer confirmation Procedure exist (MC protocol)
Local station Port No. PLC's port number
Destination IP address TELLUS' IP address
Dest. Port No. TELLUS' port number

 

Wiring

1:1 connection w/o HUB

Use a cross cable.

 

1:1 connectoin w/ HUB or 1:n connection

Use straight cables.

 

PC's IP address

Follow the procedure below to set a computer IP address.
The procedure below is provided for Windows 7

 

Procedure
  1. Go to [Start] > [Control Panel].
  2. Click [Network and Sharing Center].
  3. Click [Change adapter settings].



  4. Select [Local Area Connection] and right click it to go to [Property] from the right-click menu.

  5. Go to [Local Area Connection Properties] > [Internet Protocol Version 4 (TCP/IPv4)] and click [Properties].




  6. Set the IP address. When necessary, also set [Subnet mask] and [Default gateway].



 

TELLUS4/TELLUS3 (Ethernet settings)

Local Port Setting

This port number is used for communicating with V-Server or other stations that use SEND/EREAD/EWRITE/MES macro commands.
  * This is not used for PLC communication.

  • When own station information is registered in the Network Table in the screen program:
    Check [Use Network Table] to set the table number.
    *The IP address that is set in the Control Panel Setting on the PC is valid. 

  • When own station information is not registered in the Network Table in the screen program:
    Specify inforamtion in this dialog.

PLC COM Port

This is for setting a port number to communicate with a PLC.

  • [Specify Port No.] is checked:
    Specify a port number set in the [Device Connection Setting] > [Communication Setting] in the screen program.
    *When using an Ethernet unit and the port number is set by the Open setting on the PLC settings, this option must be ticked.

  • [Specify Port No.] is not checked:
    Unused port number is automatically assigned.

 

Was this page helpful?

Please cooperate with the questionnaire to make it better.

  • Back to FAQ top

FAQ by product

  • V10/V9 series

  • V8/TS2060 series

  • TELLUS and V-Server

Most searched FAQs

  • Communication error "Error code received"
  • I want to search where these buttons are used:
    - Screen Change-over buttons
    - Overlap Control buttons
  • Communication Error "Timeout"
  • "The port cannot be opened."
  • What PLC models can be connected?
To page top
  • » 제품에 관한 문의
  • » 영업 판매 문의
  • » 카탈로그 청구
  • » RoHS 지령에 대응

MONITOUCH

라인업
  • X1 SERIES
  • V10 SERIES
  • V9 SERIES
  • TECHNOSHOT
  • Web Machine Interface
  • Smart Editor
  • V-SFT
  • TELLUS and V-Server
서포트 »
  • 다운로드
  • 문의
  • 추천 주변기기
FAQ »
  • FAQ concerning MONITOUCH
대리점 »
  • Overseas distributors
  • » Privacy Policy
Copyright©2013 Hakko Electronics Co., Ltd. All Right Reserved