V10/V9 series Operation Troubles HKFAQ000029

date: 2017/9/13

Alarms are not saved in the alarm history as specified for [Number of Data to Save] in the alarm server settings.

 

<Cause>

The setting for [System Setting] -> [Alarm Server] -> [Data Output Setting] -> [Number of Data to Save] is small.

 

<Solution>

Increase the setting for [Number of Data to Save].
If the display mode of the alarm part is "alarm history" or "event history", each occurrence and each reset is counted as one data.
Consequently, to keep one error bit change as historical data, "2" should be set at minimum.

V9series|Alarms_are_not_saved_in_the_alarm_history_as_specified_for_[Number_of_Data_to_Save]_in_the_alarm_server_settings.

Was this page helpful?

Please cooperate with the questionnaire to make it better.

Related questions(FAQ)

  • Messages are not displayed in the alarm tracking display.
  • Back to FAQ top

FAQ by product

  • V10/V9 series

  • V8/TS2060 series

  • TELLUS and V-Server

Most searched FAQs

  • Communication error "Error code received"
  • I want to search where these buttons are used:
    - Screen Change-over buttons
    - Overlap Control buttons
  • Communication Error "Timeout"
  • "The port cannot be opened."
  • What PLC models can be connected?
To page top
  • » 제품에 관한 문의
  • » 영업 판매 문의
  • » 카탈로그 청구
  • » RoHS 지령에 대응

MONITOUCH

라인업
  • X1 SERIES
  • V10 SERIES
  • V9 SERIES
  • TECHNOSHOT
  • Web Machine Interface
  • Smart Editor
  • V-SFT
  • TELLUS and V-Server
서포트 »
  • 다운로드
  • 문의
  • 추천 주변기기
FAQ »
  • FAQ concerning MONITOUCH
대리점 »
  • Overseas distributors
  • » Privacy Policy
Copyright©2013 Hakko Electronics Co., Ltd. All Right Reserved