V9 series Operation Troubles HKFAQ000030

date: 2017/9/13

The V series does not recognize the storage device.

 

<Causes>

  1. The storage device is not supported.
  2. The file system of the storage device is not supported.
  3. The error status is set in $s497 (or $s1035 when the USB-A port is used).
  4. The storage device is faulty.
  5. The access port setting of the V series is wrong.

 

<Solutions>

  1. The following storage devices can be used with the V series.

    Type

    Capacity

    File System

    SD card

     2GB max.  FAT, FAT32

    SDHC card

     4 to 32GB  FAT32

    USB flash drive

     32GB max.  FAT, FAT32 


  2. Only storage devices with FAT or FAT32 file systems can be used with the V series.
    Check the file system using a PC and if any other file system is used, format the storage device.

  3. Check the values in system memory $s497 and $s1035. Any value other than "0" indicates an error status.
    When this system memory address is assigned to a numerical data display part, monitoring is possible.
    For more information about error codes, refer to "Storage Status".

  4. Check if it is possible to access the storage device from the PC.
    If not, use a different storage device.

  5. There are two storage device connection ports: the built in SD card slot and USB-A port. Set the port to access using V-SFT-6.
    [Setting location]
    [System Setting] -> [Other] -> [Storage Setting] -> [Storage Connection Target]

Was this page helpful?

Please cooperate with the questionnaire to make it better.

Related questions(FAQ)

  • How to check whether or not a storage is recognized
  • How to remove storage devices safely from the V9 series unit
  • Back to FAQ top

FAQ by product

  • V9 series

  • V8 series

  • TELLUS and V-Server

Most searched FAQs

  • Communication error "Error code received"
  • What PLC models can be connected?
  • Communication Error "Timeout"
  • "The port cannot be opened."
  • How to save sampling data even after turning off the TS/V series
To page top
  • » 제품에 관한 문의
  • » 영업 판매 문의
  • » 카탈로그 청구
  • » RoHS 지령에 대응

MONITOUCH

라인업
  • X1 SERIES
  • V10 SERIES
  • V9 SERIES
  • TECHNOSHOT
  • Web Machine Interface
  • V-SFT
  • TELLUS and V-Server
서포트 »
  • 다운로드
  • 문의
  • 추천 주변기기
FAQ »
  • FAQ concerning MONITOUCH
대리점 »
  • Overseas distributors
  • » Privacy Policy
Copyright©2013 Hakko Electronics Co., Ltd. All Right Reserved