date: 2024/12/2
What types of cables can be used for screen program transfer?
Screen program transfer is possible using a commercially-available USB or Ethernet cable.
 The "V-CP" or "UG00C-T1" serial transfer cable manufactured by Hakko Electronics can also be used.
The following table lists each series and the corresponding available transfer methods.
| Series | USB | Ethernet | Serial | 
| V10 V9 | 〇 | 〇*2 | 〇 | 
| TS2060(i) | 〇 | △*2*3 | 〇 | 
|  V8 |  〇 | △*3*4 | 〇 | 
| V7 UG30 | △ | △*3*5 | 〇 | 
| V6 UG20 Simple POD | × | △*6 | 〇 | 
| V4 *7 V4S UG400 UG210 | × | × | 〇 + "ADP25-M" option | 
|  GD-80 *7 | × | × | 〇 | 
| GD-80S | × | × | △*8 | 
*1 If the computer is not equipped with a serial port, use a commercially-available 
     USB-to-serial converter.
     Connect "V-CP" or "UG00C-T1" to the MJ1 port on MONITOUCH.
 *2 A straight cable can also be used with or without a hub.
 *3 Type with built-in LAN port.
 *4 When the "CU(N)-03-x","UG03I-E" communication unit is installed.
 *5 When the "CU-03-x","UG03I-E" communication unit or "DU-01","UG230A-DCL" option 
     unit is installed.
 *6 When the "CU-03-x","UG03I-E" communication unit is installed.
 *7 It is possible to make your own cable for serial transfer with the V4/GD-80/GD-81S
    /UG400/UG210/UG200 by referring to the wiring diagram. 
  
 *8 Serial transfer with the GD-80S cannot be performed using the "V-CP" or "UG00C-T1"
     cable.
     Make your own cable by referring to the wiring diagram.
  