date: 2024/9/25
How to check the communication condition between the temperature controller and the V series
The temperature controller condition is output to the system device memory of the V series.
 Check the following device memory addresses for each station number.
- Click [System Setting] -> [Hardware Setting] and display a [PLCx Properties] dialog on the V-SFT editor. Then select [Disconnect] for [Comm. Error Handling].
 
- The communication results with each station are stored in the system device memory as below.
 Assign system device memory addresses to numerical data display parts for monitoring.
 System device memory: $Pn: 100 - 355 (n: PLC1 - 8) ..... Station No. 0 - 255
 Example: When a temperature controller is registered to PLC2 as station No. 10, monitor $P2: 110.
Error details
| Code (HEX) | Description | 
| 0000H | Normal | 
| FFFFH | Timeout | 
| 8001H | Check code error | 
| 8002H | Data error | 
| 800BH |  Error code received from the | 
* The received code can be acquired at $Pn: 508 to 511. For more information, click here.
Other error codes are shown below:
 
| Error | Details | Solution | 
| Timeout | Although a request to send is given, no answer is returned within the specified time. | Take actions 1, 2, and 3. | 
| Check code | The response check code is not correct. | Take actions 1 and 3. | 
| Data error | The received code is invalid. | Take actions 1, 2, and 3. | 
| Error code received | An error is occurring at the connected device. | Refer to the PLC manual. | 
| Buffer full | The buffer of the V series is full. | Contact your HAKKO representative. | 
| Parity | A parity check error has occurred. | Take actions 2 and 3. | 
| Overrun | After one character is received, the next character is received before internal processing is completed. | Take actions 1 and 3. | 
| Framing | Although the stop bit must be "1", it is detected as "0". | Take actions 1, 2 and 3. | 
| Break detection | The SD of the connected device remains at the low level. | Check connection to the SD/RD of the connected device. | 
What to do:
- Check that communication settings of the V series match those of the connected device.
- Check the cable connection.
- Data may be disrupted because of noise. Provide protection against noise.
Was this page helpful?
Please cooperate with the questionnaire to make it better.



