V8/TS2060 series Operation Troubles HKFAQ000156

date: 2021/8/5

The PLC memory address for a part is garbled as "??" or is "blank".

 

<Causes>

  1. When the PLC model setting is changed, it is replaced with device "??".
  2. PLC2 - 8 (Temperature Control/PLC2Way with the V7 series) are set as "not used".
  3. Variable name cooperation is not accomplished with a PLC project file of Fuji Electric's MICREX-SX.

 

* If you are using the V-SFT-6, see here.

 

<Solutions>

  1. When changing the PLC model, display the [Memory Conversion] dialog and change "??" to an existing memory address under [After Conversion Start Memory].

     

    Example: Change the PLC from Mitsubishi's QnU series CPU → Fuji Electric's MICREX-SX series CPU.

    (1) After the PLC model is changed, the "Execute device conversion?" message dialog will be displayed. Click [Yes].

     

    (2) Click the "??" memory after conversion that corresponds to the "M" memory before conversion.

     

    (3) Set WM0 in the [Memory Input] dialog, and click [OK].


    "M" memory is changed so that it will start from WM0.

     

  2. Correct or delete all illegal memory addresses.
    Illegal memory addresses can be found by running an error check.

     

    Example: [Tool] → [Error Check]
    Move the cursor to the error item, and click the [Error Details] icon.
    The error details can be viewed.
    V8series|The PLC memory address for a part is garbled as ?? or is blank.

    Click the [Jump to Error Item] icon V8series|The PLC memory address for a part is garbled as ?? or is blank. to jump to the error occurring position.
    Delete or modify the illegal memory address.
    V8series|The PLC memory address for a part is garbled as ?? or is blank.

     

  3. Link up with the PLC project file.
    List of PLC models which require linkup (IEC mode only *)
    • MICREX-SX (T-link)
    • MICREX-SX (OPCN-1)
    • MICREX-SX (SX bus)
    • MICREX-SX SPH/SPB/SPM/SPE/SPF series
    • MICREX-SX SPH/SPB/SPM/SPE/SPF CPU
    • MICREX-SX (Ethernet)
      * The current mode setting can be viewed by selecting [File] → [Project]→[Select Memory].

 

Example: MICREX-SX SPH/SPB/SPM/SPE/SPF CPU "IEC mode"
V8series|The PLC memory address for a part is garbled as ?? or is blank.

 

(1) Select [File] → [Project] → [Option], and check [? Cooperating work].
V8series|The PLC memory address for a part is garbled as ?? or is blank.

 

(2) Select the PLC project file (extension ".mwt").
V8series|The PLC memory address for a part is garbled as ?? or is blank.

 

(3) Check that the correct PLC project file is displayed for [Path], and click [OK].
V8series|The PLC memory address for a part is garbled as ?? or is blank.

* Note the following points for the project name and pathname. If not, the file will not be linked correctly.

    • The following characters must not be used for the pathname.
      :, ., =, ;, <, >, [, ], /, ?, |, *, "
    • The following characters must not be used for the project name.
      ¥, :, ., =, ;, <, >, [, ], /, ?, |, *, "
    • The project name must not exceed 24 characters.
      (24 one-byte characters/12 two-byte characters, one-byte and
      two-byte characters can be used at the same time)
    • The project pathname (from the drive name to the project name) must not exceed 171 characters.

Was this page helpful?

Please cooperate with the questionnaire to make it better.

Related questions(FAQ)

  • The PLC device memory address for a part is garbled as "??" or is "blank".
  • Back to FAQ top

FAQ by product

  • V10/V9 series

  • V8/TS2060 series

  • TELLUS and V-Server

Most searched FAQs

  • Communication error "Error code received"
  • I want to search where these buttons are used:
    - Screen Change-over buttons
    - Overlap Control buttons
  • Communication Error "Timeout"
  • "The port cannot be opened."
  • What PLC models can be connected?
To page top
  • » 제품에 관한 문의
  • » 영업 판매 문의
  • » 카탈로그 청구
  • » RoHS 지령에 대응

MONITOUCH

라인업
  • X1 SERIES
  • V10 SERIES
  • V9 SERIES
  • TECHNOSHOT
  • Web Machine Interface
  • Smart Editor
  • V-SFT
  • TELLUS and V-Server
서포트 »
  • 다운로드
  • 문의
  • 추천 주변기기
FAQ »
  • FAQ concerning MONITOUCH
대리점 »
  • Overseas distributors
  • » Privacy Policy
Copyright©2013 Hakko Electronics Co., Ltd. All Right Reserved